Instructions Manual
R-MI-LU Rev.: 0 English version
Ultrasonic level
transmitter
Series LU
Vista de página 0
1 2 3 4 5 6 ... 27 28

Resumo do Conteúdo

Página 1 - Instructions Manual

Instructions Manual R-MI-LU Rev.: 0 English version Ultrasonic level transmitter Series LU

Página 2

10 3.2 Power supply and analog output connection (models LU92X) Models LU92X (LU921, LU923, LU921H) are 2-wire instruments. The connection is made i

Página 3

11 3.4 Connection examples The two usual ways to connect the alarm outputs are NPN or PNP modes, depending on if the load is connected to the positi

Página 4 - bottom

12 Once the instrument has been installed, the echo intensity can be verified. This intensity depends on the distance to the target, the type of prod

Página 5

13 4.3 Dead zone indication If the measured distance is shorter than the minimum measuring distance, we can say that the product is in the dead zone

Página 6 - 3 ELECTRICAL CONNECTION

14 5 CONFIGURATION To change a digit, touching the key () the flashing digit will be incremented. When the value of 9 is reached on the next increme

Página 7 - - mA (negative)

15 The percentage of filling is calculated taking into account the points distance to the bottom (see section 5.2) and distance to the top, according

Página 8 - Active output

16 The remaining screens will require the parameters in the chosen mode. 5.5 Current output Next, the loop current programming screens are displayed

Página 9

17 5.6 Alarms In these screens we select the actuation points of the two alarms and the level of hysteresis. By level of hysteresis we understand the

Página 10 - Terminal

18 If an activation point of 0.9 m and a deactivation point of 1 m is programmed, when the level is zero the output will be on. When the level reache

Página 11

19 5.8 Dead zone distance In some installations it can be useful to increase the dead zone value. For example, in cases of standpipe measurements. O

Página 12 - 4 OPERATION

2 TABLE OF CONTENTS 1 INTRODUCTION ... 4 2 INSTALLATION ...

Página 13

20 5.12 Serial number and software version Touching the three keys at the same time we access a screen where the serial number of the converter is s

Página 14 - 5 CONFIGURATION

21 7 HART COMMUNICATION Level meters LU9XH y LU921H have a modem for HART communication. LU transmitters are fully compatible with the HART Server so

Página 15

22 8 MAINTENANCE No special maintenance is required . For cleaning, a humid cloth can be used, and if necessary with a little soap. Solvents or other

Página 16

23 9 TECHNICAL CHARACTERISTICS 9.1 Materials Body: PP, PVDF Housing: Polycarbonate. 9.2 Process connection LU91 / LU921: G2 (BSP) thread. LU93 /

Página 17

24 10 DIMENSIONS LU91 LU921 LU93 LU923

Página 18 - ) at the same time

25 11 TROUBLESHOOTING Problem Probable cause Remedy Dashes on the display The product is in “dead zone”. The distance between the level transmitte

Página 19

26 12 CONFIGURATION DIAGRAM SN: Serial number dA: Damping dL: Dead zone distance dead: Dead zone alarm Hi: Hysteresis. Window in which the instrum

Página 20

27 A1A: Value at which the alarm 1 will activate A1d: Value at which the alarm 1 will deactivate A2A: Value at which the alarm 2 will activate A2d

Página 21 - 7 HART COMMUNICATION

28 WARRANTY Tecfluid S.A. guarantees all the products for a period of 24 months from their sale, against all faulty materials, manufacturing or perfo

Página 22 - 8 MAINTENANCE

3 5.9 Dead zone alarm ... 19 5.10 Hysteresis ...

Página 23 - 9 TECHNICAL CHARACTERISTICS

4 1 INTRODUCTION The series LU transmitters are electronic equipment based on the transmission of ultrasonic waves to measure the distance to a liqui

Página 24

5 It is not desirable that the product reaches the instrument, because build-up can form on the transducer, that would affect the measurement. 2.3 O

Página 25 - 11 TROUBLESHOOTING

6 2.4 Filling entries It is not recommended to install the level meter in the upper zone of a filling entry, because the instrument could detect the

Página 26 - 12 CONFIGURATION DIAGRAM

7 The power supply is provided by a diode bridge that allows connecting it regardless of the polarity . 3.1.2 Analog output connection Terminal +

Página 27

8 The analog output can be either active (default configuration), that means that the receptor must be passive, or passive, what means the receptor m

Página 28

9 mA: Ammeter Possibilities of connection for the power supply and analog output